FEATURES:
1. Autotuning PID, and ON/OFF control
2: 3 Digit Displaying
3. Sizes: 48 mm x 48 mm. Option: 48x96mm, 48x96mm,
72x72mm, 96x96mm
4. Universal input: TC: K, E, J, T RTD: Pt100, Cu50
5. Relay control output. SSR, SCR, PWM control output are
options
6. Main output for heating; Control output can be used for
cooling or AL2.
Specification:
Input Type
|
Thermocouple
|
K, E, J, T
|
Thermo resistance
|
Pt100, Cu50, Cu100
|
Control type It can be freely converted with Control type.
|
On/off control
|
Proportion scan 0%-3600% Integral time 0-3600S Differential time 0-3600S
|
PI control
|
PID control
|
Control output
|
R:
|
Relay: AC 250V/3A or DC 30V/3A
|
S:
|
SSR / logic control output
|
T:
|
SCR control output
|
Measuring accuracy
|
+-0.5%F.S+-1digit
|
A/D conversion
|
Dual integral
|
Sample time
|
<0.5S
|
Power supply
|
85-260VAC/DC(TA4), 220/110VAC(TA6,7,9), or 24VDC
|
Operating condition
|
0-50C 45-85%RH
|
Display
|
Two line 3 digit
|
Withstand voltage strength
|
AC 1500V 1min Between power terminal and case
|
Power supply
|
<5VA
|
Insulation resistance
|
DC 500V>50MΩ (Between power terminal and case)
|
You can change C to F in TA4. Please do as following:
1. Press UP and DOWN key at the same time, and hold for 5
seconds. You can see the parameter LSP, OSP, HY1... SCK
2. Select parameter SCK and set SCK=020. (This is a password for
modifying calibration parameters)
3: Press SET key you can see the parameter CJS, CJL, CJH and SEL
4: Select parameter SET and set SEL=010.
5. Press and hold UP and DOWN key for 5 seconds to return to the
measure state.
6. Press SET key for 3 seconds you can see the parameters AL1,
AM1...C-F...
7. Select parameter C-F and set C-F=F